

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Overload release current setting
500.0 - 1250A
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Yes
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Degree of protection (IP)
IP30
Integrated earth fault protection
No
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Motor drive optional
Yes
Motor drive integrated
No
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range short-term delayed short-circuit release
750.0 - 750.0A
Rated permanent current Iu
1250A
With under voltage release
No
From same serie
1SDA056076R1 | E2L 1250 PR122/P-LSI IN=1250A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Overload release current setting
500.0 .. 1250A
Device construction
Built-in device slide-in technique (withdrawable)
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Degree of protection (IP)
IP30
Integrated earth fault protection
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Motor drive optional
Motor drive integrated
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range short-term delayed short-circuit release
750.0 .. 750.0A
Rated permanent current Iu
1250A
With under voltage release
From same serie
We use cookies to enhance your experience.