Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Rated permanent current Iu
1600A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
640.0 - 1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Rated voltage
690 - 690V
Motor drive integrated
No
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Motor drive optional
Yes
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
1SDA056092R1 | E2L 1600 PR122/P-LSI IN=1600A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Rated permanent current Iu
1600A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
640.0 .. 1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Rated voltage
690 .. 690V
Motor drive integrated
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Motor drive optional
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30