Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of control elementPush button
Number of poles4
Type of electrical connection of main circuitBolt connection
Degree of protection (IP)IP30
Integrated earth fault protectionYes
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitBack side
Adjustment range short-term delayed short-circuit release960.0 - 960.0A
Overload release current setting640.0 - 1600A
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
With switched-off indicatorYes
Adjustment range undelayed short-circuit release2400.0 - 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz130kA
Motor drive optionalYes
Rated permanent current Iu1600A
Device constructionBuilt-in device fixed built-in technique
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056095R1 | E2L 1600 PR123/P-LSIG IN=1600A 4P F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of control element

Push button

Number of poles

4

Type of electrical connection of main circuit

Bolt connection

Degree of protection (IP)

IP30

Integrated earth fault protection

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Back side

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Overload release current setting

640.0 .. 1600A

Motor drive integrated

Suitable for DIN rail (top hat rail) mounting

Rated voltage

690 .. 690V

With switched-off indicator

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Motor drive optional

Rated permanent current Iu

1600A

Device construction

Built-in device fixed built-in technique

With under voltage release

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.