Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
960.0 - 960.0A
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Yes
Overload release current setting
640.0 - 1600A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Number of poles
3
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Motor drive integrated
No
From same serie
1SDA056101R1 | E2L 1600 PR122/P-LSIG IN=1600A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Overload release current setting
640.0 .. 1600A
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Number of poles
3
Degree of protection (IP)
IP30
Complete device with protection unit
Motor drive integrated
From same serie