Technical specifications

Type of electrical connection of main circuitBolt connection
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
Overload release current setting1000.0 - 2500A
Position of connection for main current circuitBack side
Number of poles4
Integrated earth fault protectionNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
With under voltage releaseNo
Rated permanent current Iu2500A
Adjustment range undelayed short-circuit release3750.0 - 37500A
Type of control elementPush button
Complete device with protection unitYes
Number of auxiliary contacts as change-over contact4
Adjustment range short-term delayed short-circuit release2500 - 25000A
Motor drive integratedNo
Rated voltage690 - 690V
Degree of protection (IP)IP30
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056120R1 | E3N 2500 PR121/P-LI IN=2500A 4P F H

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

With switched-off indicator

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Overload release current setting

1000.0 .. 2500A

Position of connection for main current circuit

Back side

Number of poles

4

Integrated earth fault protection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

With under voltage release

Rated permanent current Iu

2500A

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Type of control element

Push button

Complete device with protection unit

Number of auxiliary contacts as change-over contact

4

Adjustment range short-term delayed short-circuit release

2500 .. 25000A

Motor drive integrated

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Motor drive optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.