Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Overload release current setting
1280.0 - 3200A
Motor drive integrated
No
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Adjustment range short-term delayed short-circuit release
3200 - 32000A
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Position of connection for main current circuit
Back side
Motor drive optional
Yes
Type of control element
Push button
Degree of protection (IP)
IP30
Rated voltage
690 - 690V
Rated permanent current Iu
3200A
With switched-off indicator
Yes
1SDA056146R1 | E3N 3200 PR121/P-LSIG IN=3200A 3P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Overload release current setting
1280.0 .. 3200A
Motor drive integrated
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Number of poles
3
Position of connection for main current circuit
Back side
Motor drive optional
Type of control element
Push button
Degree of protection (IP)
IP30
Rated voltage
690 .. 690V
Rated permanent current Iu
3200A
With switched-off indicator