Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Motor drive optional
Yes
With switched-off indicator
Yes
Number of poles
3
Motor drive integrated
No
Complete device with protection unit
Yes
Adjustment range short-term delayed short-circuit release
3200 - 32000A
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Overload release current setting
1280.0 - 3200A
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
From same serie
1SDA056160R1 | E3N 3200 PR121/P-LI IN=3200A 3P W M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Motor drive optional
With switched-off indicator
Number of poles
3
Motor drive integrated
Complete device with protection unit
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Overload release current setting
1280.0 .. 3200A
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA