Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA056213R1 | E3S 1600 PR122/P-LSIG IN=1600A 3P F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Type of control element
Push button
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Rated voltage
690 .. 690V
Number of poles
3
Rated permanent current Iu
1600A
Overload release current setting
640.0 .. 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
With switched-off indicator
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
With under voltage release
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Complete device with protection unit