Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Rated permanent current Iu
1600A
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Type of control element
Push button
1SDA056233R1 | E3S 1600 PR121/P-LSI IN=1600A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Rated permanent current Iu
1600A
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Complete device with protection unit
Motor drive optional
Type of control element
Push button