Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
800.0 - 2000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
2000A
Adjustment range short-term delayed short-circuit release
2000 - 20000A
With under voltage release
No
Integrated earth fault protection
No
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Rated voltage
690 - 690V
Motor drive optional
Yes
With switched-off indicator
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Number of poles
3
From same serie
1SDA056256R1 | E3S 2000 PR121/P-LI IN=2000A 3P W M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
800.0 .. 2000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
2000A
Adjustment range short-term delayed short-circuit release
2000 .. 20000A
With under voltage release
Integrated earth fault protection
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Rated voltage
690 .. 690V
Motor drive optional
With switched-off indicator
Complete device with protection unit
Degree of protection (IP)
IP30
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Number of poles
3
From same serie