Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Rated permanent current Iu
2500A
Device construction
Built-in device fixed built-in technique
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Adjustment range short-term delayed short-circuit release
2500 .. 25000A
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Degree of protection (IP)
IP30
Overload release current setting
1000.0 .. 2500A
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
With under voltage release
Number of poles
4
Motor drive optional
Motor drive integrated
Position of connection for main current circuit
Back side
Complete device with protection unit