Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
1500.0 - 1500.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device fixed built-in technique
Overload release current setting
1000.0 - 2500A
Number of poles
4
With under voltage release
No
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Type of control element
Push button
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Position of connection for main current circuit
Back side
Motor drive optional
Yes
Degree of protection (IP)
IP30
With switched-off indicator
Yes
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Bolt connection
From same serie
1SDA056285R1 | E3S 2500 PR122/P-LSIG IN=2500A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
1500.0 .. 1500.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Overload release current setting
1000.0 .. 2500A
Number of poles
4
With under voltage release
Rated voltage
690 .. 690V
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Type of control element
Push button
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Position of connection for main current circuit
Back side
Motor drive optional
Degree of protection (IP)
IP30
With switched-off indicator
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Bolt connection
From same serie