Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of electrical connection of main circuitConnection at separate chassis part
Rated permanent current Iu2500A
Rated voltage690 - 690V
With switched-off indicatorYes
Position of connection for main current circuitConnection at separate chassis part
Overload release current setting1000.0 - 2500A
Adjustment range short-term delayed short-circuit release2500 - 25000A
Degree of protection (IP)IP30
Type of control elementPush button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz75kA
Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
Number of poles3
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release3750.0 - 37500A
Integrated earth fault protectionYes
With under voltage releaseNo
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056290R1 | E3S 2500 PR121/P-LSIG IN=2500A 3P W

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of electrical connection of main circuit

Connection at separate chassis part

Rated permanent current Iu

2500A

Rated voltage

690 .. 690V

With switched-off indicator

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

1000.0 .. 2500A

Adjustment range short-term delayed short-circuit release

2500 .. 25000A

Degree of protection (IP)

IP30

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

75kA

Motor drive integrated

Number of auxiliary contacts as change-over contact

4

Number of poles

3

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Integrated earth fault protection

With under voltage release

Motor drive optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.