Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Adjustment range short-term delayed short-circuit release
3200 - 32000A
Rated permanent current Iu
3200A
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Back side
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Integrated earth fault protection
No
Motor drive integrated
No
Motor drive optional
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
1280.0 - 3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
From same serie
1SDA056313R1 | E3S 3200 PR121/P-LSI IN=3200A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
Rated permanent current Iu
3200A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Back side
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Integrated earth fault protection
Motor drive integrated
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
1280.0 .. 3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
From same serie