Technical specifications
Rated permanent current Iu
3200A
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Rated voltage
690 - 690V
Overload release current setting
1280.0 - 3200A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
1920.0 - 1920.0A
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
1SDA056325R1 | E3S 3200 PR122/P-LSIG IN=3200A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Rated voltage
690 .. 690V
Overload release current setting
1280.0 .. 3200A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Number of poles
3