Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA056332R1 | E3S 3200 PR122/P-LSI IN=3200A 4P W

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
Motor drive optional
Complete device with protection unit
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Integrated earth fault protection
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Degree of protection (IP)
IP30
Rated permanent current Iu
3200A
Motor drive integrated
Type of electrical connection of main circuit
Connection at separate chassis part
Type of control element
Push button
With switched-off indicator
Overload release current setting
1280.0 .. 3200A