Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
480.0 - 480.0A
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
800A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Integrated earth fault protection
Yes
Rated voltage
690 - 690V
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Device construction
Built-in device fixed built-in technique
Number of poles
3
From same serie
1SDA056341R1 | E3H 800 PR122/P-LSIG IN=800A 3P F H

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
480.0 .. 480.0A
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
800A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Integrated earth fault protection
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Motor drive optional
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
Complete device with protection unit
Degree of protection (IP)
IP30
Device construction
Built-in device fixed built-in technique
Number of poles
3