Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range undelayed short-circuit release1875.0 - 18750A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Overload release current setting500.0 - 1250A
Rated permanent current Iu1250A
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release1250 - 12500A
Rated voltage690 - 690V
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Type of control elementPush button
Number of poles3
Complete device with protection unitYes
Motor drive optionalYes
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056368R1 | E3H 1250 PR121/P-LI IN=1250A 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Overload release current setting

500.0 .. 1250A

Rated permanent current Iu

1250A

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

1250 .. 12500A

Rated voltage

690 .. 690V

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

With under voltage release

DIN rail (top hat rail) mounting optional

Type of control element

Push button

Number of poles

3

Complete device with protection unit

Motor drive optional

Degree of protection (IP)

IP30

Position of connection for main current circuit

Back side

Motor drive integrated

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.