Technical specifications
Overload release current setting
640.0 - 1600A
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Back side
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
With under voltage release
No
Motor drive optional
Yes
With switched-off indicator
Yes
Number of poles
3
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
1SDA056402R1 | E3H 1600 PR121/P-LSIG IN=1600A 3P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 .. 1600A
Rated voltage
690 .. 690V
Integrated earth fault protection
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Back side
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
With under voltage release
Motor drive optional
With switched-off indicator
Number of poles
3
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Degree of protection (IP)
IP30