Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
With switched-off indicator
Yes
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
1280.0 - 3200A
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Yes
Adjustment range short-term delayed short-circuit release
1920.0 - 1920.0A
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
From same serie
1SDA056503R1 | E3H 3200 PR123/P-LSIG IN=3200A 3P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
With switched-off indicator
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
1280.0 .. 3200A
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
From same serie