Technical specifications

Degree of protection (IP)IP30
Rated voltage690 - 690V
Rated permanent current Iu800A
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
With switched-off indicatorYes
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Number of poles3
Position of connection for main current circuitBack side
Overload release current setting320.0 - 800A
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release480.0 - 480.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz130kA
Adjustment range undelayed short-circuit release1200.0 - 12000A
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056535R1 | E3V 800 PR123/P-LSIG IN=800A 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)

IP30

Rated voltage

690 .. 690V

Rated permanent current Iu

800A

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Type of control element

Push button

With switched-off indicator

Motor drive integrated

Number of auxiliary contacts as normally closed contact

0

Number of poles

3

Position of connection for main current circuit

Back side

Overload release current setting

320.0 .. 800A

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

480.0 .. 480.0A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Device construction

Built-in device fixed built-in technique

Motor drive optional

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.