Aleta.hr
Main Product Image

1SDA056540R1 | E3V 800 PR122/P-LSI IN=800A 4P F HR

Code: 1593127

ManufacturerRAZNO
Catalog number1SDA056540R1
Type
EAN code8015644578800

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Number of poles

4

Overload release current setting

320.0 - 800A

Position of connection for main current circuit

Back side

Suitable for DIN rail (top hat rail) mounting

No

Rated voltage

690 - 690V

With switched-off indicator

Yes

Complete device with protection unit

Yes

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

Adjustment range undelayed short-circuit release

1200.0 - 12000A

Integrated earth fault protection

No

Adjustment range short-term delayed short-circuit release

480.0 - 480.0A

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

No

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

No

Motor drive optional

Yes

Degree of protection (IP)

IP30

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA056540R1 | E3V 800 PR122/P-LSI IN=800A 4P F HR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Number of poles

4

Overload release current setting

320.0 .. 800A

Position of connection for main current circuit

Back side

Suitable for DIN rail (top hat rail) mounting

Rated voltage

690 .. 690V

With switched-off indicator

Complete device with protection unit

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

480.0 .. 480.0A

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP30