Technical specifications

Rated permanent current Iu1600A
Number of poles3
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Overload release current setting640.0 - 1600A
Rated voltage690 - 690V
Position of connection for main current circuitBack side
Type of electrical connection of main circuitBolt connection
Type of control elementPush button
Motor drive integratedNo
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz130kA
Adjustment range short-term delayed short-circuit release1600 - 16000A
Adjustment range undelayed short-circuit release2400.0 - 24000A
Complete device with protection unitYes
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device fixed built-in technique
With under voltage releaseNo
Integrated earth fault protectionNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056593R1 | E3V 1600 PR121/P-LSI IN=1600A 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1600A

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Overload release current setting

640.0 .. 1600A

Rated voltage

690 .. 690V

Position of connection for main current circuit

Back side

Type of electrical connection of main circuit

Bolt connection

Type of control element

Push button

Motor drive integrated

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Adjustment range short-term delayed short-circuit release

1600 .. 16000A

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Complete device with protection unit

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

With under voltage release

Integrated earth fault protection