Technical specifications

Rated permanent current Iu1600A
Overload release current setting640.0 - 1600A
Number of poles3
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Degree of protection (IP)IP30
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz130kA
Motor drive integratedNo
Type of control elementPush button
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release2400.0 - 24000A
Adjustment range short-term delayed short-circuit release960.0 - 960.0A
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionYes
Position of connection for main current circuitConnection at separate chassis part
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056613R1 | E3V 1600 PR122/P-LSIG IN=1600A 3P W MP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1600A

Overload release current setting

640.0 .. 1600A

Number of poles

3

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Degree of protection (IP)

IP30

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Motor drive integrated

Type of control element

Push button

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive optional

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Position of connection for main current circuit

Connection at separate chassis part