Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
1000.0 - 2500A
Rated permanent current Iu
2500A
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
2500 - 25000A
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 - 690V
Motor drive optional
Yes
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Motor drive integrated
No
With switched-off indicator
Yes
Degree of protection (IP)
IP30
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
From same serie
1SDA056658R1 | E3V 2500 PR121/P-LSIG IN=2500A 3P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
1000.0 .. 2500A
Rated permanent current Iu
2500A
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
2500 .. 25000A
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 .. 690V
Motor drive optional
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of poles
3
Motor drive integrated
With switched-off indicator
Degree of protection (IP)
IP30
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
From same serie