Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Rated permanent current Iu
2500A
Overload release current setting
1000.0 - 2500A
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
No
Adjustment range short-term delayed short-circuit release
2500 - 25000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Number of poles
4
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
From same serie
1SDA056665R1 | E3V 2500 PR121/P-LSI IN=2500A 4P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Rated permanent current Iu
2500A
Overload release current setting
1000.0 .. 2500A
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
2500 .. 25000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Number of poles
4
DIN rail (top hat rail) mounting optional
Motor drive integrated
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
From same serie
We use cookies to enhance your experience.