Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated voltage
690 - 690V
Rated permanent current Iu
3200A
Overload release current setting
1280.0 - 3200A
Adjustment range short-term delayed short-circuit release
3200 - 32000A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Motor drive optional
Yes
Type of control element
Push button
Motor drive integrated
No
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
1SDA056697R1 | E3V 3200 PR121/P-LSI IN=3200A 4P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated voltage
690 .. 690V
Rated permanent current Iu
3200A
Overload release current setting
1280.0 .. 3200A
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Back side
Complete device with protection unit
Motor drive optional
Type of control element
Push button
Motor drive integrated
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
We use cookies to enhance your experience.