Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu3200A
Overload release current setting1280.0 - 3200A
Number of poles3
Rated voltage690 - 690V
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz130kA
Adjustment range short-term delayed short-circuit release3200 - 32000A
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release4800.0 - 48000A
With under voltage releaseNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionYes
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056706R1 | E3V 3200 PR121/P-LSIG IN=3200A 3P W MP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

3200A

Overload release current setting

1280.0 .. 3200A

Number of poles

3

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

Type of electrical connection of main circuit

Connection at separate chassis part

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Adjustment range short-term delayed short-circuit release

3200 .. 32000A

With switched-off indicator

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

With under voltage release

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Motor drive optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.