Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated permanent current Iu
2000A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
1200.0 - 1200.0A
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Overload release current setting
800.0 - 2000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
With under voltage release
No
Type of control element
Push button
Motor drive integrated
No
Integrated earth fault protection
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Number of poles
4
From same serie
1SDA056748R1 | E3L 2000 PR122/P-LSI IN=2000A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
130kA
Rated permanent current Iu
2000A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
1200.0 .. 1200.0A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Overload release current setting
800.0 .. 2000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
With under voltage release
Type of control element
Push button
Motor drive integrated
Integrated earth fault protection
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
Number of poles
4