Technical specifications

Rated permanent current Iu2500A
Number of poles3
Overload release current setting1000.0 - 2500A
Number of auxiliary contacts as change-over contact4
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release3750.0 - 37500A
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
Position of connection for main current circuitBack side
With under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz130kA
Type of control elementPush button
Type of electrical connection of main circuitBolt connection
Device constructionBuilt-in device fixed built-in technique
Degree of protection (IP)IP30
Motor drive optionalYes
With switched-off indicatorYes
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release2500 - 25000A
Rated voltage690 - 690V
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056753R1 | E3L 2500 PR121/P-LSI IN=2500A 3P F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

2500A

Number of poles

3

Overload release current setting

1000.0 .. 2500A

Number of auxiliary contacts as change-over contact

4

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Motor drive integrated

Suitable for DIN rail (top hat rail) mounting

Complete device with protection unit

Position of connection for main current circuit

Back side

With under voltage release

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

130kA

Type of control element

Push button

Type of electrical connection of main circuit

Bolt connection

Device construction

Built-in device fixed built-in technique

Degree of protection (IP)

IP30

Motor drive optional

With switched-off indicator

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

2500 .. 25000A

Rated voltage

690 .. 690V

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.