Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
4000A
Rated voltage
690 - 690V
With under voltage release
No
Device construction
Built-in device fixed built-in technique
Overload release current setting
1600.0 - 4000A
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Adjustment range short-term delayed short-circuit release
4000 - 40000A
With switched-off indicator
Yes
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Yes
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Integrated earth fault protection
No
From same serie
1SDA056792R1 | E4S 4000 PR121/P-LI IN=4000A 4P F H

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
4000A
Rated voltage
690 .. 690V
With under voltage release
Device construction
Built-in device fixed built-in technique
Overload release current setting
1600.0 .. 4000A
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Adjustment range short-term delayed short-circuit release
4000 .. 40000A
With switched-off indicator
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Integrated earth fault protection
From same serie