Technical specifications
1SDA056906R1 | E4V 3200 PR121/P-LSIG IN=3200A 4P W MP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
1280.0 .. 3200A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
3200 .. 32000A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Complete device with protection unit
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Motor drive integrated
Type of control element
Push button
Motor drive optional
With switched-off indicator
Number of poles
4
Rated permanent current Iu
3200A