Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA057013R1 | E6H 6300 PR122/P-LSIG IN=6300A 3P F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Motor drive integrated
Number of poles
3
Rated permanent current Iu
6300A
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
2520.0 .. 6300A
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
3780.0 .. 3780.0A
DIN rail (top hat rail) mounting optional
With under voltage release
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Motor drive optional
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Complete device with protection unit