Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu6300A
Rated voltage690 - 690V
Overload release current setting2520.0 - 6300A
Adjustment range short-term delayed short-circuit release3780.0 - 3780.0A
Adjustment range undelayed short-circuit release9450.0 - 94500A
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally closed contact0
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
DIN rail (top hat rail) mounting optionalNo
Position of connection for main current circuitBack side
With switched-off indicatorYes
Device constructionBuilt-in device fixed built-in technique
Number of poles4
Type of control elementPush button
Degree of protection (IP)IP30
Motor drive optionalYes
Complete device with protection unitYes
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA057023R1 | E6H 6300 PR123/P-LSIG IN=6300A 4P F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

6300A

Rated voltage

690 .. 690V

Overload release current setting

2520.0 .. 6300A

Adjustment range short-term delayed short-circuit release

3780.0 .. 3780.0A

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as normally closed contact

0

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

DIN rail (top hat rail) mounting optional

Position of connection for main current circuit

Back side

With switched-off indicator

Device construction

Built-in device fixed built-in technique

Number of poles

4

Type of control element

Push button

Degree of protection (IP)

IP30

Motor drive optional

Complete device with protection unit

Motor drive integrated

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.