Technical specifications
Rated permanent current Iu
6300A
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Adjustment range short-term delayed short-circuit release
3780.0 - 3780.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive integrated
No
Degree of protection (IP)
IP30
Type of control element
Push button
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Complete device with protection unit
Yes
With switched-off indicator
Yes
Overload release current setting
2520.0 - 6300A
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
1SDA057031R1 | E6H 6300 PR123/P-LSIG IN=6300A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
6300A
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Adjustment range short-term delayed short-circuit release
3780.0 .. 3780.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive integrated
Degree of protection (IP)
IP30
Type of control element
Push button
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Complete device with protection unit
With switched-off indicator
Overload release current setting
2520.0 .. 6300A
DIN rail (top hat rail) mounting optional
Motor drive optional