Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
6300 - 63000A
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
6300A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
2520.0 - 6300A
Adjustment range undelayed short-circuit release
9450.0 - 94500A
With switched-off indicator
Yes
Rated voltage
690 - 690V
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Motor drive integrated
No
With under voltage release
No
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
Number of poles
4
Motor drive optional
Yes
From same serie
1SDA057033R1 | E6H 6300 PR121/P-LSI IN=6300A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
6300 .. 63000A
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
6300A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
2520.0 .. 6300A
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
With switched-off indicator
Rated voltage
690 .. 690V
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Motor drive integrated
With under voltage release
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Number of poles
4
Motor drive optional
From same serie
We use cookies to enhance your experience.