Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA057107R1 | E6V 5000 PR122/P-LI IN=5000A 3P F HR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Motor drive integrated
Degree of protection (IP)
IP30
Type of control element
Push button
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
2000.0 .. 5000A
Rated permanent current Iu
5000A
Number of poles
3
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
3000.0 .. 3000.0A
DIN rail (top hat rail) mounting optional
With under voltage release
Complete device with protection unit
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Suitable for DIN rail (top hat rail) mounting
Motor drive optional