Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA057113R1 | E6V 5000 PR121/P-LSI IN=5000A 4P F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
5000A
Overload release current setting
2000.0 .. 5000A
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Type of control element
Push button
With switched-off indicator
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Back side
Rated voltage
690 .. 690V
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
5000 .. 50000A
DIN rail (top hat rail) mounting optional