Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
5000A
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
5000 - 50000A
Overload release current setting
2000.0 - 5000A
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 - 690V
Motor drive optional
Yes
Motor drive integrated
No
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Number of poles
4
With switched-off indicator
Yes
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
1SDA057114R1 | E6V 5000 PR121/P-LSIG IN=5000A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
5000A
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
5000 .. 50000A
Overload release current setting
2000.0 .. 5000A
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 .. 690V
Motor drive optional
Motor drive integrated
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Number of poles
4
With switched-off indicator
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Complete device with protection unit
Degree of protection (IP)
IP30
We use cookies to enhance your experience.