Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
5000A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2000.0 - 5000A
Adjustment range short-term delayed short-circuit release
3000.0 - 3000.0A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Motor drive integrated
No
Type of control element
Push button
Complete device with protection unit
Yes
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Yes
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
1SDA057124R1 | E6V 5000 PR122/P-LSI IN=5000A 3P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
5000A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2000.0 .. 5000A
Adjustment range short-term delayed short-circuit release
3000.0 .. 3000.0A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Motor drive integrated
Type of control element
Push button
Complete device with protection unit
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
We use cookies to enhance your experience.