Technical specifications
Rated voltage
690 - 690V
Rated permanent current Iu
5000A
Position of connection for main current circuit
Connection at separate chassis part
Overload release current setting
2000.0 - 5000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Type of control element
Push button
With under voltage release
No
Complete device with protection unit
Yes
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Adjustment range short-term delayed short-circuit release
3000.0 - 3000.0A
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
No
1SDA057135R1 | E6V 5000 PR123/P-LSIG IN=5000A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Rated permanent current Iu
5000A
Position of connection for main current circuit
Connection at separate chassis part
Overload release current setting
2000.0 .. 5000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Type of control element
Push button
With under voltage release
Complete device with protection unit
Motor drive optional
DIN rail (top hat rail) mounting optional
Motor drive integrated
Adjustment range short-term delayed short-circuit release
3000.0 .. 3000.0A
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting