Technical specifications
Rated voltage
690 .. 690V
Overload release current setting
2520.0 .. 6300A
Integrated earth fault protection
Rated permanent current Iu
6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
6300 .. 63000A
DIN rail (top hat rail) mounting optional
Type of control element
Push button
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Degree of protection (IP)
IP30
Complete device with protection unit
Position of connection for main current circuit
Back side
Motor drive optional
Number of poles
3
Number of auxiliary contacts as change-over contact
4