Technical specifications
Rated permanent current Iu
6300A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2520.0 - 6300A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
3780.0 - 3780.0A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Type of control element
Push button
Motor drive integrated
No
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Integrated earth fault protection
Yes
From same serie
1SDA057143R1 | E6V 6300 PR123/P-LSIG IN=6300A 3P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
6300A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
2520.0 .. 6300A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
3780.0 .. 3780.0A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Type of control element
Push button
Motor drive integrated
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
Integrated earth fault protection
From same serie