Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu6300A
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release3780.0 - 3780.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Adjustment range undelayed short-circuit release9450.0 - 94500A
Number of auxiliary contacts as normally open contact0
Suitable for DIN rail (top hat rail) mountingNo
Overload release current setting2520.0 - 6300A
Integrated earth fault protectionNo
With switched-off indicatorYes
Type of control elementPush button
Complete device with protection unitYes
Motor drive optionalYes
Number of poles4
Position of connection for main current circuitBack side
Degree of protection (IP)IP30
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA057147R1 | E6V 6300 PR122/P-LI IN=6300A 4P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Rated permanent current Iu

6300A

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Adjustment range short-term delayed short-circuit release

3780.0 .. 3780.0A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Number of auxiliary contacts as normally open contact

0

Suitable for DIN rail (top hat rail) mounting

Overload release current setting

2520.0 .. 6300A

Integrated earth fault protection

With switched-off indicator

Type of control element

Push button

Complete device with protection unit

Motor drive optional

Number of poles

4

Position of connection for main current circuit

Back side

Degree of protection (IP)

IP30

Motor drive integrated

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4