Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
2520.0 - 6300A
Rated permanent current Iu
6300A
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Adjustment range short-term delayed short-circuit release
3780.0 - 3780.0A
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Yes
Degree of protection (IP)
IP30
Number of poles
4
Motor drive optional
Yes
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive integrated
No
With under voltage release
No
Position of connection for main current circuit
Back side
1SDA057151R1 | E6V 6300 PR123/P-LSIG IN=6300A 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
2520.0 .. 6300A
Rated permanent current Iu
6300A
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Adjustment range short-term delayed short-circuit release
3780.0 .. 3780.0A
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Degree of protection (IP)
IP30
Number of poles
4
Motor drive optional
Complete device with protection unit
Type of control element
Push button
Motor drive integrated
With under voltage release
Position of connection for main current circuit
Back side