Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting2520.0 - 6300A
Number of poles3
Rated voltage690 - 690V
Rated permanent current Iu6300A
Number of auxiliary contacts as change-over contact4
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
Motor drive integratedNo
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Integrated earth fault protectionYes
Adjustment range short-term delayed short-circuit release6300 - 63000A
Adjustment range undelayed short-circuit release9450.0 - 94500A
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
With under voltage releaseNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA057154R1 | E6V 6300 PR121/P-LSIG IN=6300A 3P W

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

2520.0 .. 6300A

Number of poles

3

Rated voltage

690 .. 690V

Rated permanent current Iu

6300A

Number of auxiliary contacts as change-over contact

4

Type of electrical connection of main circuit

Connection at separate chassis part

Type of control element

Push button

Motor drive integrated

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

6300 .. 63000A

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Suitable for DIN rail (top hat rail) mounting

Motor drive optional

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

With under voltage release

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.