Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 - 480.0A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Overload release current setting
320.0 - 800A
Rated voltage
690 - 690V
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
Motor drive integrated
No
With switched-off indicator
Yes
Position of connection for main current circuit
Back side
From same serie
1SDA058293R1 | E2S 800 PR122/P-LI IN=800A 4P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 .. 480.0A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Overload release current setting
320.0 .. 800A
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Motor drive integrated
With switched-off indicator
Position of connection for main current circuit
Back side
From same serie