Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Device construction
Built-in device fixed built-in technique
Overload release current setting
320.0 - 800A
Rated permanent current Iu
800A
Integrated earth fault protection
No
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 - 480.0A
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
Position of connection for main current circuit
Back side
With under voltage release
No
Number of poles
4
With switched-off indicator
Yes
Motor drive optional
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
1SDA058294R1 | E2S 800 PR122/P-LSI IN=800A 4P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Device construction
Built-in device fixed built-in technique
Overload release current setting
320.0 .. 800A
Rated permanent current Iu
800A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 .. 480.0A
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Position of connection for main current circuit
Back side
With under voltage release
Number of poles
4
With switched-off indicator
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP30
We use cookies to enhance your experience.