Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
320.0 - 800A
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
800 - 8000A
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
No
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Yes
Number of poles
3
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
From same serie
1SDA058299R1 | E2S 800 PR121/P-LSI IN=800A 3P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
320.0 .. 800A
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
800 .. 8000A
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of poles
3
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0