

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
1280.0 - 3200A
Rated voltage
690 - 690V
Rated permanent current Iu
3200A
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
1920.0 - 1920.0A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Number of poles
3
With under voltage release
No
Type of control element
Push button
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive optional
Yes
Motor drive integrated
No
Position of connection for main current circuit
Back side
Adjustment range undelayed short-circuit release
4800.0 - 48000A
1SDA058729R1 | E3H 3200 PR122/P-LSIRC IN=3200A 3P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
1280.0 .. 3200A
Rated voltage
690 .. 690V
Rated permanent current Iu
3200A
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
1920.0 .. 1920.0A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Number of poles
3
With under voltage release
Type of control element
Push button
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive optional
Motor drive integrated
Position of connection for main current circuit
Back side
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
We use cookies to enhance your experience.